High-voltage direct current

Electric power transmission system

Read the original on Wikipedia ↗ Last updated from Wikipedia: 29 November 2026

Nelson River Bipoles 1 and 2 Terminus at Rosser.jpg
Long distance HVDC lines carrying hydroelectricity from Canada's Nelson River (opens on Wikipedia) to this converter station (opens on Wikipedia) where it is converted to AC for use in southern Manitoba (opens on Wikipedia)'s grid Image: J. Lindsay, CC BY-SA 3.0, via Wikimedia Commons

A high-voltage direct current (HVDC) system uses direct current (opens on Wikipedia) (DC) and high voltages (currently between 100 kV (opens on Wikipedia) and 800 kV) for electric power transmission (opens on Wikipedia). It contrasts with the more common alternating current (opens on Wikipedia) (AC) transmission systems.[1]

HVDC lines are commonly used for long-distance power transmission, since they require fewer conductors and incur less power loss than equivalent AC lines. HVDC also allows power transmission between AC transmission systems that are not synchronized (opens on Wikipedia). Since the power flow through an HVDC link can be controlled independently of the phase angle between source and load, it can stabilize a network against disturbances due to rapid changes in power. HVDC also allows the transfer of power between grid systems running at different frequencies, such as 50 and 60 Hz. This improves the stability and economy of each grid by allowing the exchange of power between previously incompatible networks.

The modern form of HVDC transmission uses technology developed extensively in the 1930s in Sweden (ASEA (opens on Wikipedia)) and in Germany. Early commercial installations included one in the Soviet Union in 1951 between Moscow and Kashira (opens on Wikipedia), and a 100 kV, 20 MW system between Gotland (opens on Wikipedia) and mainland Sweden in 1954.[2] The longest HVDC link in the world is the Zhundong–South Anhui link in China, a ±1,100 kV, ultra HVDC line with a length of more than 3,000 km (1,900 mi).[3]

Powerlines, Washoe County, Nevada (3070983825).jpg
The towers of the Pacific DC Intertie (opens on Wikipedia), the longest HVDC line in the United States. Image: brewbooks from near Seattle, USA, CC BY-SA 2.0, via Wikimedia Commons
HVDC Europe.svg
HVDC links in Europe
  Existing links
  Under construction
  Proposed
Many of these HVDC lines transfer power from renewable sources such as hydro and wind. For names, see also the annotated version. (opens on Wikipedia) Image: J JMesserly and those stated in source., CC BY-SA 3.0, via Wikimedia Commons

High voltage is used for electric power (opens on Wikipedia) transmission to reduce the energy lost in the resistance (opens on Wikipedia) of the wires. For a given quantity of power (opens on Wikipedia) transmitted, doubling the voltage will deliver the same power at only half the current:

Since the energy lost as heat in the wires is directly proportional to the square of the current using half the current at double the voltage reduces the line losses by a factor of 4.[a] While energy lost in transmission can also be reduced by decreasing the resistance by increasing the conductor size, larger conductors are heavier and more expensive.

High voltage cannot readily be used for lighting or motors, so transmission-level voltages must be reduced for end-use equipment. Transformers (opens on Wikipedia) are used to change the voltage levels in alternating current (opens on Wikipedia) (AC) transmission circuits, but cannot pass DC current. Transformers make AC voltage changes practical, and AC generators are more efficient than those using DC. These advantages led to early low-voltage DC transmission systems being supplanted by AC systems around the turn of the 20th century.[4]

Practical conversion of current between AC and DC became possible with the development of power electronics (opens on Wikipedia) devices such as mercury-arc valves (opens on Wikipedia) and, starting in the 1970s, power semiconductor devices (opens on Wikipedia) including thyristors (opens on Wikipedia), integrated gate-commutated thyristors (opens on Wikipedia) (IGCTs), MOS-controlled thyristors (opens on Wikipedia) (MCTs) and insulated-gate bipolar transistors (opens on Wikipedia) (IGBT).[5]

Electromechanical systems

Thury HVDC system.svg
Schematic diagram of a Thury HVDC transmission system Image: User:J JMesserly. This conversion to an SVG file is a derivative work of a public domain image from the 1919 US book Electric Power Transmission. For permissions on the original work, see license information for the PNG file listed in "other versions". My minor contribution (conversion to SVG and mi, CC BY 3.0, via Wikimedia Commons
Image not shown for licensing reasons. View on Wikipedia
HVDC in 1971: this 150 kV mercury-arc valve (opens on Wikipedia) converted AC hydropower voltage for transmission to distant cities from Manitoba Hydro (opens on Wikipedia) generators.
HVDCPylons.jpg
Pylons of the Baltic Cable (opens on Wikipedia) HVDC in Sweden Image: Timberwind, CC BY-SA 3.0, via Wikimedia Commons

The first long-distance transmission of electric power was demonstrated using direct current in 1882 in the 57 km Miesbach-Munich Power Transmission (opens on Wikipedia), but only 1.5 kW was transmitted.[6] An early method of HVDC transmission was developed by the Swiss engineer René Thury (opens on Wikipedia)[7] and his method, the Thury system, was put into practice by 1889 in Italy by the Acquedotto De Ferrari-Galliera company. This system used series-connected motor-generator (opens on Wikipedia) sets to increase the voltage. Each set was insulated from electrical ground (opens on Wikipedia) and driven by insulated shafts from a prime mover (opens on Wikipedia). The transmission line was operated in a constant-current (opens on Wikipedia) mode, with up to 5,000 volts across each machine, some machines having double commutators (opens on Wikipedia) to reduce the voltage on each commutator. This system transmitted 630 kW at 14 kV DC over a distance of 120 kilometres (75 mi).[8][9] The Moutiers–Lyon (opens on Wikipedia) system transmitted 8,600 kW of hydroelectric power a distance of 200 kilometres (120 mi), including 10 kilometres (6.2 mi) of underground cable (opens on Wikipedia). This system used eight series-connected generators with dual commutators for a total voltage of 150 kV between the positive and negative poles, and operated from c.1906 until 1936. Fifteen Thury systems were in operation by 1913.[10] Other Thury systems operating at up to 100 kV DC worked into the 1930s, but the rotating machinery required high maintenance and had high energy loss.

Various other electromechanical devices (opens on Wikipedia) were tested during the first half of the 20th century with little commercial success.[11] One technique attempted for conversion of direct current from a high transmission voltage to lower utilization voltage was to charge series-connected batteries (opens on Wikipedia), then reconnect the batteries in parallel to serve distribution loads.[12] While at least two commercial installations were tried around the turn of the 20th century, the technique was not generally useful owing to the limited capacity of batteries, difficulties in switching between series and parallel configurations, and the inherent energy inefficiency of a battery charge/discharge cycle.[b]

Mercury arc valves

First proposed in 1914,[13] the grid controlled mercury-arc valve (opens on Wikipedia) became available during the period 1920 to 1940 for the rectifier (opens on Wikipedia) and inverter (opens on Wikipedia) functions associated with DC transmission. Starting in 1932, General Electric (opens on Wikipedia) tested mercury-vapor valves and a 12 kV DC transmission line, which also served to convert 40 Hz generation to serve 60 Hz loads, at Mechanicville, New York (opens on Wikipedia). In 1941, a 60 MW, ±200 kV, 115 km (71 mi) buried cable link, known as the Elbe-Project (opens on Wikipedia), was designed for the city of Berlin (opens on Wikipedia) using mercury arc valves but, owing to the collapse of the German government in 1945, the project was never completed.[14] The nominal justification for the project was that, during wartime, a buried cable would be less conspicuous as a bombing target. The equipment was moved to the Soviet Union and was put into service there as the Moscow–Kashira HVDC system.[15] The Moscow–Kashira system and the 1954 connection by Uno Lamm (opens on Wikipedia)'s group at ASEA (opens on Wikipedia) between the mainland of Sweden and the island of Gotland (opens on Wikipedia) marked the beginning of the modern era of HVDC transmission.[6]

Mercury arc valves were common in systems designed up to 1972, the last mercury arc HVDC system (the Nelson River Bipole 1 system (opens on Wikipedia) in Manitoba (opens on Wikipedia), Canada) having been put into service in stages between 1972 and 1977.[16] Since then, all mercury arc systems have been either shut down or converted to use solid-state devices. The last HVDC system to use mercury arc valves was the Inter-Island HVDC link (opens on Wikipedia) between the North and South Islands of New Zealand, which used them on one of its two poles. The mercury arc valves were decommissioned on 1 August 2012, ahead of the commissioning of replacement thyristor converters.

Thyristor valves

The development of thyristor valves for HVDC began in the late 1960s. The first complete HVDC scheme based on thyristor was the Eel River (opens on Wikipedia) scheme in Canada, which was built by General Electric (opens on Wikipedia) and went into service in 1972.[17]

Since 1977, new HVDC systems have used solid-state devices (opens on Wikipedia), in most cases thyristors (opens on Wikipedia). Like mercury arc valves, thyristors require connection to an external AC circuit in HVDC applications to turn them on and off. HVDC using thyristors is also known as line-commutated converter (LCC) HVDC.

On March 15, 1979, a 1920 MW thyristor based direct current connection between Cabora Bassa and Johannesburg (1,410 km; 880 mi) was energized. The conversion equipment was built in 1974 by Allgemeine Elektricitäts-Gesellschaft AG (AEG) (opens on Wikipedia), and Brown, Boveri & Cie (opens on Wikipedia) (BBC) and Siemens (opens on Wikipedia) were partners in the project. Service interruptions of several years were a result of a civil war in Mozambique.[18] The transmission voltage of ±533 kV was the highest in the world at the time.[6]

Capacitor-commutated converters

Line-commutated converters have some limitations in their use for HVDC systems. This results from requiring a period of reverse voltage to affect the turn off. An attempt to address these limitations is the capacitor-commutated converter (CCC). The CCC has series capacitors (opens on Wikipedia) inserted into the AC line connections. CCC has remained only a niche application because of the advent of voltage-source converters (VSCs) which more directly address turn-off issues.

Voltage-source converters

Widely used in motor drives (opens on Wikipedia) since the 1980s, voltage-source converters (VSCs) started to appear in HVDC in 1997 with the experimental Hellsjön–Grängesberg (opens on Wikipedia) project in Sweden. By the end of 2011, this technology had captured a significant proportion of the HVDC market.

The development of higher rated insulated-gate bipolar transistors (opens on Wikipedia) (IGBTs), gate turn-off thyristors (opens on Wikipedia) (GTOs), and integrated gate-commutated thyristors (opens on Wikipedia) (IGCTs), has made HVDC systems more economical and reliable. This is because modern IGBTs incorporate a short-circuit failure mode, wherein should an IGBT fail, it is mechanically shorted. Therefore, modern VSC HVDC converter stations (opens on Wikipedia) are designed with sufficient redundancy to guarantee operation over their entire service lives. The manufacturer Hitachi Energy (opens on Wikipedia) (formerly Hitachi ABB Power Grids and ABB (opens on Wikipedia) earlier) calls this concept HVDC Light,[19] while Siemens (opens on Wikipedia) calls a similar concept HVDC PLUS (Power Link Universal System) similarly General Electric Vernova (opens on Wikipedia) (Alstom (opens on Wikipedia), a part of General Electric (opens on Wikipedia) later) call their product based upon this technology as HVDC MaxSine. In addition to this, Toshiba (opens on Wikipedia) calls their product as HVDC-VSC MMC*1 technology[20] and Mitsubishi Electric (opens on Wikipedia) call their product as HVDC Diamond.[21] They have extended the use of HVDC down to blocks as small as a few tens of megawatts and overhead lines as short as a few dozen kilometers. There are several different variants of VSC technology: most installations built until 2012 use pulse-width modulation (opens on Wikipedia) in a circuit that is effectively an ultra-high-voltage motor drive. More recent installations, including HVDC PLUS and HVDC MaxSine, are based on variants of a converter called a modular multilevel converter (MMC).

Multilevel converters have the advantage that they allow harmonic (opens on Wikipedia) filtering equipment to be reduced or eliminated altogether. By way of comparison, AC harmonic filters of typical line-commutated converter stations cover nearly half of the converter station area.

With time, voltage-source converter systems will probably replace all installed simple thyristor-based systems, including the highest DC power transmission applications.[5]